GEKKO 2L
- 2 loops panel
- Supports connection to Repeaters via RS422, Fibre-Optic or TCP/IP
- Networkable panel, compatible with OCTO+ and NODE+ range of panels
- Up to 250 devices per loop (only 125 addresses available)
- Up to 95 VULCAN 2 (addressable) ultra low current base sounders (32 address limit)
- 32 individually programmable sounder addresses
- Full Self-Addressable Devices support
- 2 Fire output relays (change-over) and 1 Fault relay (NC – opens on fault)
- 2 conventional alarm outputs (Individually programmable)
- Both detection loops monitored for integrity
- 512 fully programmable sounder and I/O groups
- 384 fully programmable zones
- Event log (rolling, 10000 entries)
- Available only with ZEOS protocol
- Compatible with all our own low cost ancillary modules
Mains Power Supply Rating | 90V AC to 230V AC |
---|---|
Primary Dc Supply | 28.5V DC @ 2.4 A (Max) |
Secondary Supply | 21.6 Min. – 27.2V DC (Max) – Battery charger: 27.5V DC |
Battery Capacity (Internal) | Standard box: 2x 12V 7AH; Deep Box: for larger volume batteries |
Aux Power Outpu | 2 x 24V DC 300mA / 1 x 24V switched out |